April 15, 2007

                             []< ET NEWS                                
====================================================================== 
    NEWS AND INFORMATION FOR THE FIRE PROTECTION ENGINEERING TEAM     
---------------------------------------------------------------------- 
Issue No. 284    ISSN 1554-074X      http://www.etnews.org   4-15-2007 
====================================================================== 
 
Contents
--------
- News
- ET News Journal
- Job Opportunities
- Seminar Schedule
- Comments & Acknowledgements 

====================================================================== 
NEWS
====================================================================== 

***INTERESTING VIDEO***

Office Fires: Danger Ignored By Many
CBS News - New York City,NY,USA
"There's a lot of apathy to responding immediately to a fire alarm
signal," Fannin agreed. "I think very few, if any, office workers have
a plan." ...
http://www.cbsnews.com/stories/2007/04/13/earlyshow/contributors/susan
koeppen/main2679946.shtml

---------------------------------------------------------------------- 

James M. Shannon to Join Osteotech Board of Directors
PR Newswire (press release) - New York,NY,USA
Mr. Shannon is currently the President and Chief Executive Officer of
the National Fire Protection Association ("NFPA"), an international
organization which ...
http://www.prnewswire.com/cgi-bin/stories.pl?ACCT=104&STORY=/www/story
/04-11-2007/0004563811&EDATE=

---------------------------------------------------------------------- 

House approves sprinkler requirements for care facilities
Belleville News-Democrat - Belleville,IL,USA
Earlier this session, the Senate approved a measure that would require
many care facilities to install full fire alarm systems by August 2009
http://www.belleville.com/mld/belleville/news/state/17062024.htm

---------------------------------------------------------------------- 
 
On April 13th, our daughter Sarah gave birth to April Kristine Baker,
making Friday the 13th a lucky day for the Baker family. 

I'll see you in Colorado Springs this week at the Automatic Fire Alarm
Association annual meeting.  We'll be celebrating the 55th anniversary
of the AFAA. 
http://www.afaa.org/ 

Have fun! 

Mike 
mailto:mike@etnews.org 

======================================================================
                            ADVERTISEMENT                             
======================================================================
 CENTRAL STATION MONITORING                   UL(r) listed monitoring 
 All major formats plus AES, SafeCom, ScanAlert, & Video Verification
  *** 2007 New Dealer Special - 1 YEAR FREE ADDITIONAL SERVICES ***
 Free Web Access                         mailto://begeord@cuaccess.net
 503-630-8961 voice || 503-630-8944 fax  http://www.csmul.com
======================================================================
ET NEWS JOURNAL
======================================================================

IBC-2006 Fire Alarm Changes
---------------------------

[F]907.2 Where required.
An approved manual, automatic or manual and automatic fire alarm
system installed in accordance with the provisions of this code and
NFPA 72 shall be provided in new buildings and structures in
accordance with Sections 907.2.1 through 907.2.23 and provide occupant
notification in accordance with Section 907.9, unless other
requirements are provided by another section of this code. Where
automatic sprinkler protection installed in accordance with Section
903.3.1.1 or 903.3.1.2 is provided and connected to the building fire
alarm system, automatic heat detection required by this section shall
not be required. The automatic fire detectors shall be smoke 
detectors. Where ambient conditions prohibit installation of automatic 
smoke detection, other automatic fire detection shall be allowed.
(DEFERS THE REQUIREMENT TO INSTALL A FIRE ALARM SYSTEM TO ARTICLES
907.2.1 THROUGH 907.2.23)
(WHERE A FIRE ALARM SYSTEM IS REQUIRED, USE IT TO NOTIFY OCCUPANTS
IN ACCORDANCE WITH 907.9)

[F]907.2.1 Group A.
A manual fire alarm system shall be installed in Group A occupancies
having an occupant load of 300 or more. Portions of Group E
occupancies occupied for assembly purposes shall be provided with a
fire alarm system as required for the Group E occupancy.
(REMOVED REDUNDANT "...IN ACCORDANCE WITH NFPA 72...")

[F] 907.2.3 Group E.
Exception 3. Manual fire alarm boxes shall not be required in Group E
occupancies where the building is equipped throughout with an approved
automatic sprinkler system, the notification appliances will activate
on sprinkler water flow and manual activation is provided from a
normally occupied location.
(NEW)

[F] 907.2.6.2 Group I-2.
Corridors in nursing homes (both intermediate care and skilled nursing
facilities), detoxification facilities and spaces permitted to be open
to the corridors by Section 407.2 shall be equipped with an automatic
fire detection system. Hospitals shall be equipped with smoke
detection as required in Section 407.2.
(LAST SENTENCE REGARDING HOSPITALS IS NEW)

[F] 907.2.7 Group M.
A manual fire alarm system shall be installed in Group M occupancies
having an occupant load of 500 or more persons or more than 100
persons above or below the lowest level of exit discharge. The
initiation of a signal from a manual fire alarm box shall initiate
alarm notification appliances as required by Section 907.9.
(REDUNDANT COVERED MALL REQUIREMENT REMOVED)

[F] 907.2.7.1 (Group M) Occupant notification.
During times that the building is occupied, the initiation of a signal
from a manual fire alarm box or from a water flow switch shall not be
required to activate the alarm notification appliances when an alarm
signal is activated at a constantly attended location from which
evacuation instructions shall be initiated over an emergency
voice/alarm communication system installed in accordance with Section
907.2.12.2.
(RE-WORDED)

[F] 907.2.9 Group R-2.
A manual fire alarm system shall be installed
in Group R-2 ...
Exception 2.3. At least one manual fire alarm box is installed at an
approved location.
(EXCEPTION 2.3 REMOVED)

[F] 907.2.10 Single- and multiple-station smoke alarms.
Listed single- and multiple-station smoke alarms complying with UL 217
shall be installed in accordance with the provisions of this code and
the household fire-warning equipment provisions of NFPA 72.
(NEW REQUIREMENT FOR SMOKE ALARMS TO COMPLY WITH UL 217)

[F] 907.2.10.1.3 (Smoke Alarms) Group I-1.
Single- or multiple-station smoke alarms shall be installed and
maintained in sleeping areas in Group I-1 occupancies.
Exception: Single- or multiple-station smoke alarms shall not be
required where the building is equipped throughout with an automatic
fire detection system in accordance with Section 907.2.6.
(2003 EXCEPTION LANGUAGE TURNED INTO AN ACTUAL EXCEPTION)

[F] 907.2.12.2 (High Rise Building) Emergency voice/alarm 
communication system.
The operation of any automatic fire detector, sprinkler water-flow
device or manual fire alarm box shall automatically sound an alert
tone followed by voice instructions giving approved information and
directions for a general or staged evacuation on a minimum of the
alarming floor, the floor above and the floor below in accordance with
the building's fire safety and evacuation plans required by Section
404 of the International Fire Code. Speakers shall be provided
throughout the building by paging zones. As a minimum, paging zones
shall be provided as follows:
1. Elevator groups.
2. Exit stairways.
3. Each floor.
4. Areas of refuge as defined in Section 1002.1.
(MORE SPECIFIC EVAC LANGUAGE REFERENCING IFC ARTICLE 404)
(SPEAKERS REQUIRED IN ELEVATOR GROUPS VERSUS ELEVATOR LOBBIES)
(SPEAKERS IN CORRIDORS REMOVED)
(SPEAKERS IN TENANT SPACES OVER 1000 FT^2 REMOVED)
(SPEAKERS IN R-2 SLEEPING AND DWELLING UNITS REMOVED)
(SPEAKERS IN R-1 SLEEPING UNITS REMOVED)
(EXCEPTION FOR I-1 AND I-2 OCCUPANCIES REMOVED)

[F] 907.2.12.2.1 (High Rise Building EVAC) Manual override.
A manual override for emergency voice communication shall be provided
on a selective and all-call basis for all paging zones.
(ADDED "...ON A SELECTIVE AND ALL-CALL BASIS...")

[F] 907.2.12.2.2 (High Rise Building EVAC) Live voice messages.
The emergency voice/alarm communication system shall also have the
capability to broadcast live voice messages through paging zones on a
selective and all-call basis.
(REPLACED SPECIFIC SPEAKER LOCATIONS WITH ""...PAGING ZONES..."

[F] 907.2.17 Lumber, wood structural panel and veneer mills.
Lumber, wood structural panel and veneer mills shall be provided with
a manual fire alarm system.
(REPLACED "LUMBER" WITH "WOOD STRUCTURAL PANEL")

[F] 907.3.1 (Manual Fire Alarm Boxes) Location.
Exception: Manual fire alarm boxes shall not be required in Group E
occupancies where the building is equipped throughout with an approved
automatic sprinkler system, the notification appliances will activate
on sprinkler water flow and manual activation is provided from a
normally occupied location.
(REDUNDANT EXCEPTION REMOVED)

[F] 907.3.5 (Manual Fire Alarm Boxes) Protective covers.
The fire code official is authorized to require the installation of
listed manual fire alarm box protective covers to prevent malicious
false alarms or to provide the manual fire alarm box with protection
from physical damage. The protective cover shall be transparent or red
in color with a transparent face to permit visibility of the manual
fire alarm box. Each cover shall include proper operating 
instructions. A protective cover that emits a local alarm signal shall 
not be installed unless approved.
(REPLACED "BUILDING OFFICIAL" WITH "FIRE CODE OFFICIAL"

[F] 907.7 Presignal system.
Presignal systems shall not be installed unless approved by the fire
code official and the fire department. Where a presignal system is
installed, 24-hour personnel supervision shall be provided at a
location approved by the fire department, in order that the alarm
signal can be actuated in the event of fire or other emergency.
(REPLACED "BUILDING OFFICIAL" WITH "FIRE CODE OFFICIAL")

[F] 907.8.2 (Zones) High-rise buildings.
In buildings with a floor used for human occupancy that is located
more than 75 feet (22 860 mm) above the lowest level of fire
department vehicle access, a separate zone by floor shall be provided
for all of the following types of alarm-initiating devices where
provided:
(RE-WORDED TO READ "...A FLOOR USED FOR HUMAN OCCUPANCY...")

[F] 907.9.1.2 (Alarm Notification Appliances) Employee work areas.
Where employee work areas have audible alarm coverage, the
notification appliance circuits serving the employee work areas shall
be initially designed with a minimum of 20 percent spare capacity to
account for the potential of adding visible notification appliances in
the future to accommodate hearing impaired employees.
(REPLACED THE NEBULOUS "...CAN BE INTEGRATED..." WITH "...MINIMUM OF
20% SPARE CAPACITY...")

[F] 907.14 Monitoring.
Fire alarm systems required by this chapter or the International Fire
Code shall be monitored by an approved supervising station in
accordance with NFPA 72.
(RE-WORDED) 

====================================================================== 
                            ADVERTISEMENT                             
====================================================================== 
LIGHT ENGINEERED DISPLAYS, INC.       UL, CSFM and MEA Listed Products 
Graphic and Directory Annunciators    Firefighter Smoke Control Panels 
AquaALERT Water Leak Detection   ARA Systems, Protective Device Covers 
       Complete catalog and specifications available on request        
800-251-2512     -       FAX 800-251-9878       -       www.ledinc.com 
======================================================================
JOB OPPORTUNITIES
====================================================================== 

JOB OPPORTUNITY and SEEKING EMPLOYMENT announcements are provided as a
service. ET News provides a venue for direct contact between job
seekers and employers. ET News is not a placement agency and does not
endorse either job seekers or employers.

--

Send your announcement to: mailto:jobs@etnews.org or post your own ad:
http://www.etnews.org/index.php?s=257 

======================================================================
SEMINAR SCHEDULE
======================================================================

------------------   
April 25, 2007 Missoula, MT  
------------------ 
Understanding IBC Fire Alarm Requirements   
Contact Bruce Hadella for more information:
mailto:bhadella@montana.edu 
(406) 771-4338

------------------   
April 27, 2007 Great Falls, MT  
------------------ 
Understanding IBC Fire Alarm Requirements   
Contact Bruce Hadella for more information:
mailto:bhadella@montana.edu 
(406) 771-4338

------------------   
May 2-3, 2007 Orlando, FL  
------------------ 
Intermediate Fire Alarm Seminar (NICET I & II) 
http://www.afaa.org/pdf/IntFA_LakeMary_May2007.pdf 

------------------   
May 22-23, 2007 Denver, CO  
------------------ 
Intermediate Fire Alarm Seminar (NICET I & II) 
Including Denver Amendments 
http://www.afaa.org/pdf/IntFA_Denver_May2007.pdf 

------------------   
June 19-21, 2007 Cincinnati, OH  
------------------ 
Understanding IBC Fire Alarm Requirements  
Fire Alarm Plan Review 
Inspection and Testing of Fire Alarm Systems 
http://www.afaa.org/pdf/IBC_PR_TI_Cincinnati_Jun2006.pdf 

======================================================================
COMMENTS AND ACKNOWLEDGEMENTS
======================================================================

ET News is written nearly every week and almost always sent on Sunday.

Doug Hockinson built the PHP/MySQL ET News website -> http://phpvs.com

Subscribe to Moore-Wilson Signaling report -> http://tinyurl.com/5y23n

Purchase NICET Element Review Handbooks -->  http://tinyurl.com/2qllsm

Purchase NFPA, ICC, and more on line http://etnews.org/index.php?s=461

Purchase new & used codes & standards on eBay http://tinyurl.com/36zzk

----------------------------------------------------------------------
Some information may be found in this message and etnews.org that is 
reprinted with permission from one or more of the following; NFPA 70 
National Electrical Code(r), NFPA 72(r) National Fire Alarm Code(r), 
NFPA 101(r) Life Safety Code(r), Copyright(c) NFPA, Quincy, MA 02269 
This reprinted material is not the complete and official position of 
the NFPA on the referenced subject, which is represented only by the 
standard in its entirety. 
======================================================================
+--------------------------------------------------------------------+
|                   Michael Baker & Associates Inc                   |
| (800) 734-3902 || PO Box 737, Gladstone OR 97027 || mba@etnews.org |
+--------------------------------------------------------------------+
ET News(SM) Copyright(c) 2007 by Michael B. Baker. All rights reserved
1,324 subscribers
Send a link to a friend        
 

 

Home - Clients - Book Store - NICET Level I - NICET Level II - NICET Level III - NICET Level IV - Glossary - External Links - Licensing - Photographs - Employment - Disney Crud(SM) - Archives 2001 - Archives 2002 - Archives 2003 - Archives 2004 - Archives 2005 - Archives 2006 - Archives 2007 - Archives 2008 - Archives 2009 - Archives 2010 - Archives 2011 - Archives 2012 - Archives 2013 - Misc

ET NewsSM content copyright © 2017
by Michael B. Baker. All rights reserved.
ISSN 1554-074X

RSS Content
Some information may be found within this web site that is reprinted with permission from one or more of the following: NFPA 70 National Electrical Code®,NFPA 72® National Fire Alarm Code®, & NFPA 101® Life Safety Code®, Copyright© NFPA, Quincy, MA 02269.

This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety.